Modbus polling cycle calculator

Quick answer: a Modbus RTU scan cycle is set by frame time, not by the PLC. At 9,600 baud, one 25-register read costs roughly 90–120 ms once slave latency and the inter-frame gap are counted — so ten devices land near a one-second cycle no matter how fast the master polls. Put your numbers in; the frame math is below the result.

Inputs

Requests are split at the Modbus limit of 125 registers per read.
Time from end of request to start of response. 5–20 ms is typical for modern slaves; old meters can be far slower.

Result

Requests per device–
Time per request–
Cycle per device–
Full scan cycle (all devices)–
Achievable scan rate–
–

How it is calculated

Each request/response pair costs: request frame (8 bytes) + response frame (5 + 2 × registers in that request bytes), sent at 11 bits per byte (1 start, 8 data, parity, 1 stop). Add the slave latency and the Modbus inter-frame gap of 3.5 character times (1.75 ms fixed above 19,200 baud). Retries, exception responses and write traffic are not counted — treat the result as the best case a healthy bus can reach.